This is what Madison Water Utility reported to the state and EPA. It is not a test of the water at your tap, which your home's pipes and fixtures can change. Information only, not medical advice. Data sources and method
Depth Score · partial
Below limits, some above health goals
TapDepth's rating of public data, not a safety finding. As of Nov 2026, method 1.2. How the score works
From results reported by Madison Water Utility, sampled Sep 2023 to Nov 2026. Not a test of your tap.
- Health55%92
- Pipes20%Not included
Not in our data yet: utilities' lead service line inventories haven't been added.
- Track record15%72
- Everyday water10%50
How this score was worked out
Health
Each substance's average over its latest year of samples, compared with its legal limit and health goal. Up to 10 points off each. Volatile organic chemicals count as one group, by the worst one, and so do pesticides and industrial chemicals, and nitrate with nitrate + nitrite. Lead and copper use the 90th percentile of home tap samples and the action level.
| Substance | Average | Legal limit | Health goal | Rule | Points |
|---|---|---|---|---|---|
| Chlorine (total residual) | 0.3872 mg/L (116 samples, Nov 2025 to Nov 2026) | 4 mg/L | 4 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Arsenic | 0.0207 µg/L (28 samples, Oct 2025 to Oct 2026) | 10 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | −2 |
| Nitrate (as nitrogen) | 1.3 mg/L (21 samples, Jun 2026 to Oct 2026) | 10 mg/L | 10 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Fluoride | 0.6891 mg/L (49 samples, Dec 2025 to Nov 2026) | 4 mg/L | 4 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Total trihalomethanes | 3.44 µg/L (12 samples, Oct 2025 to Oct 2026) | 80 µg/L | None set | No health goal: counts from half the limit | 0 |
| Benzene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Carbon tetrachloride | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichlorobenzene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 600 µg/L | 600 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,4-Dichlorobenzene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 75 µg/L | 75 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichloroethane | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1-Dichloroethylene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 7 µg/L | 7 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| cis-1,2-Dichloroethylene | 0.1125 µg/L (8 samples, Oct 2026 to Oct 2026) | 70 µg/L | 70 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| trans-1,2-Dichloroethylene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Dichloromethane | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichloropropane | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Ethylbenzene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 700 µg/L | 700 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Chlorobenzene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Styrene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Tetrachloroethylene | 0.795 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | −3.3 |
| Toluene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 1,000 µg/L | 1,000 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2,4-Trichlorobenzene | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 70 µg/L | 70 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1,1-Trichloroethane | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 200 µg/L | 200 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1,2-Trichloroethane | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 3 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Trichloroethylene | 0.1187 µg/L (8 samples, Oct 2026 to Oct 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | Not counted (group) |
| Vinyl chloride | 0 µg/L (8 samples, Oct 2026 to Oct 2026) | 2 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Xylenes (total) | 0.0375 µg/L (8 samples, Oct 2026 to Oct 2026) | 10,000 µg/L | 10,000 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Lead | 1.8 µg/L (1 sample, Sep 2023 to Sep 2023) | 15 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | −3 |
Track record
100, minus 25 for each health-based violation in the last 5 years (here 1), 10 for each from 5 to 10 years ago (0) and 3 for each missed or late test, report or notice (1). Boil water notices aren't in our data yet.
Everyday water
Hardness (as calcium carbonate) 349 mg/L: 50.
PFAS
PFAS are not counted until EPA's PFAS limits take effect. EPA currently lists April 2029 for PFOA and PFOS, and has proposed moving that to 2031. PFAS results are shown separately.
PFAS outlook: upcoming EPA limits
Not yet enforceable. EPA lists April 2029 and has proposed 2031.
PFOA or PFOS was detected, with every sample point's one-year average at or below EPA's upcoming 4 ng/L limit.
Latest sample August 12, 2026. Highest sample point one-year average, counted the rule's way: 0 ng/L (74 samples at 24 sample points, Dec 2022 to Oct 2026).
Latest sample September 15, 2026. Highest sample point one-year average, counted the rule's way: 0 ng/L (74 samples at 24 sample points, Dec 2022 to Oct 2026).
Bars show the latest sample. The line marks EPA's upcoming limit of 4 ng/L each.
Reported by Madison Water Utility, sampled September 15, 2026.
Averaged the way EPA's rule describes (each sample point's one-year average), using the results we have. The rule counts results below 4 ng/L (parts per trillion) as zero in that average. Our data may not include every sample point, and only regulators decide compliance.
The PFAS outlook is not a compliance finding and does not change the Depth Score. It covers PFOA and PFOS, the two PFAS limits EPA has said it plans to keep. Results from untreated source water are left out.
substances with a recent sample
in the latest samples
since Nov 2016
paperwork and monitoring, since Nov 2016
Current results
27 substancesSubstances with drinking water limits, from the last six years of samples. Highest recent sample shown.
- Chlorine (total residual)0.38 mg/LReported by Madison Water Utility, sampled November 13, 2026.Sample point: Distribution SystemWhat is chlorine and chloramine?
- Arsenic0.58 µg/LReported by Madison Water Utility, sampled October 6, 2026.EPA's health goal for this substance is zero.Sample point: Entry Point, well BF508What is arsenic?
- Nitrate (as nitrogen)3.82 mg/LReported by Madison Water Utility, sampled June 1, 2026.Sample point: Entry Point, well BF513What is nitrate?
- Fluoride0.85 mg/LReported by Madison Water Utility, sampled June 1, 2026.Sample point: Entry Point, well BF512What is fluoride?
- Total trihalomethanes7.4 µg/LReported by Madison Water Utility, sampled October 13, 2026.Sample point: Distribution SystemWhat is total trihalomethanes?
- BenzeneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is benzene?
- Carbon tetrachlorideNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is carbon tetrachloride?
- 1,2-DichlorobenzeneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,2-Dichlorobenzene?
- 1,4-DichlorobenzeneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,4-Dichlorobenzene?
- 1,2-DichloroethaneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,2-Dichloroethane?
- 1,1-DichloroethyleneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,1-Dichloroethylene?
- cis-1,2-Dichloroethylene0.38 µg/LReported by Madison Water Utility, sampled October 20, 2026.Sample point: Entry Point, well BF511What is cis-1,2-Dichloroethylene?
- trans-1,2-DichloroethyleneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is trans-1,2-Dichloroethylene?
- DichloromethaneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is dichloromethane?
- 1,2-DichloropropaneNot detected (below 0.25 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,2-Dichloropropane?
- EthylbenzeneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF518What is ethylbenzene?
- ChlorobenzeneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is chlorobenzene?
- StyreneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is styrene?
- Tetrachloroethylene1.6 µg/LReported by Madison Water Utility, sampled October 21, 2026.EPA's health goal for this substance is zero.Sample point: Entry Point, well BF518What is tetrachloroethylene?
- TolueneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is toluene?
- 1,2,4-TrichlorobenzeneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,2,4-Trichlorobenzene?
- 1,1,1-TrichloroethaneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,1,1-Trichloroethane?
- 1,1,2-TrichloroethaneNot detected (below 0.5 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is 1,1,2-Trichloroethane?
- Trichloroethylene0.28 µg/LReported by Madison Water Utility, sampled October 21, 2026.EPA's health goal for this substance is zero.Sample point: Entry Point, well BF518What is trichloroethylene?
- Vinyl chlorideNot detected (below 0.2 µg/L)Reported by Madison Water Utility, sampled October 21, 2026.Sample point: Entry Point, well BF506What is vinyl chloride?
- Xylenes (total)0.3 µg/LReported by Madison Water Utility, sampled October 20, 2026.Sample point: Entry Point, well BF509What is xylenes?
- Lead1.8 µg/LReported by Madison Water Utility, sampled September 30, 2023.EPA's health goal for this substance is zero.Sample point: 90th percentile of home tap samples the system collected, Jun 2023 to Sep 2023What is lead?
PFAS ("forever chemicals")
29 substancesEPA set limits for some PFAS in 2024. They aren't enforceable yet, so they're shown as upcoming limits and never in warning colors.
- PFOA2.1 ng/LReported by Madison Water Utility, sampled August 12, 2026.Sample point: Entry Point, well BF514What is PFOA?
- PFOS2 ng/LReported by Madison Water Utility, sampled September 15, 2026.Sample point: Entry Point, well BF516What is PFOS?
- PFHxS6.1 ng/LReported by Madison Water Utility, sampled September 15, 2026.Sample point: Entry Point, well BF506What is PFHxS?
- PFNANot detected (below 1.9 ng/L)Reported by Madison Water Utility, sampled October 20, 2026.Sample point: Entry Point, well BF515What is PFNA?
- HFPO-DA (GenX)Not detected (below 1.9 ng/L)Reported by Madison Water Utility, sampled October 20, 2026.Sample point: Entry Point, well BF515What is genX (HFPO-DA)?
- PFBS2.9 ng/LReported by Madison Water Utility, sampled August 12, 2026.Sample point: Entry Point, well BF514What is PFBS?
- PFBA46.5 ng/LReported by Madison Water Utility, sampled April 4, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFPeANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFHxANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFHpANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFDANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFUnANot detected (below 2 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFDoANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFTrDANot detected (below 7 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFTANot detected (below 8 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFPeSNot detected (below 4 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFHpSNot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFMPANot detected (below 4 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFMBANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- PFEESANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- NFDHANot detected (below 20 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- ADONANot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- 9Cl-PF3ONSNot detected (below 2 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- 11Cl-PF3OUdSNot detected (below 5 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- 4:2 FTSNot detected (below 3 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- 6:2 FTSNot detected (below 5 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- 8:2 FTSNot detected (below 5 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- NEtFOSAANot detected (below 5 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
- NMeFOSAANot detected (below 6 ng/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is other PFAS?
Other monitored substances
3 substancesSubstances EPA asked systems to test for to decide future rules. Most have no limit yet.
- LithiumNot detected (below 9 µg/L)Reported by Madison Water Utility, sampled October 8, 2024.Sample point: Entry Point to Dist. SystemWhat is lithium?
- Hardness (as calcium carbonate)500 mg/LReported by Madison Water Utility, sampled June 1, 2026.Sample point: Entry Point, well BF514What is hardness?
- Sodium65.6 mg/LReported by Madison Water Utility, sampled June 1, 2026.Sample point: Entry Point, well BF514What is sodium?
These figures were reported by the water system to its regulators. They are not a test of the water at this address. Compliance is judged on averages over time, so one sample above a limit does not by itself mean a system is out of compliance. For a test of your own tap, use a state-certified laboratory. Units: ng/L is nanograms per liter, the same as parts per trillion (ppt); µg/L is micrograms per liter, the same as parts per billion (ppb); mg/L is milligrams per liter, the same as parts per million (ppm).
Violations since Nov 2016
Recorded by the state and EPAHealth-based
A drinking water limit or treatment requirement was not met.
- Violation recorded by the state for Oct 2024 to Dec 2024LEAD AND COPPER RULE REVISIONS · Lead and Copper Rule Revisions · Status: resolved
Testing and reporting
A required test or report was missed or late. This is about paperwork and monitoring, and does not by itself mean the water was unsafe.
None recordedNotices and other requirements
A required notice to customers was missed or late.
- Public Notification Violation for NPDWR Violation (Oct 2024 to Oct 2025)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
On the map
Nearby water providers, colored by Depth ScoreLoading the map…
Open on the mapYearly water quality report
We don't have a link to this provider's yearly water quality report yet. Providers that serve homes send one to customers every year by July 1, and you can ask the provider for a copy.
Where the water comes from
No water purchases from another system are recorded.
Service lines (pipes from the water main to buildings)
As reported by MADISON WATER UTILITY to Wisconsin, in EPA's records as of the third quarter of 2026: 2 lead, 0 galvanized needing replacement, 0 material not yet identified, 65,534 non-lead.
Galvanized needing replacement: galvanized lines that are or were connected to lead pipe, which the rule says must be replaced.
Non-lead counts may be incomplete: EPA doesn't require them until November 2027.
A lead or galvanized service line can add lead to water, but it doesn't mean there is lead in your water. These counts cover the whole system, not your address. Ask your water system whether your home's line is on its inventory.
U.S. EPA, SDWIS/Fed Service Line Inventory report, data as of November 21, 2026
Historical results (2012-2019)
Lab results states sent EPA for 2012-2019, compiled by EPA for its Six-Year Review of drinking water rules, not for compliance decisions. They are more than six years old, so they may not reflect the water today, and they are never mixed with current results.
- ArsenicLatest: not detected · 19 of 45 samples detected · highest 0.805 µg/L (June 7, 2017) · legal limit 10 µg/LHistorical result, sampled July 10, 2018. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Wisconsin to EPA.
- Nitrate (as nitrogen)Latest: 0.24 mg/L · 83 of 136 samples detected · highest 4.28 mg/L (June 11, 2013) · legal limit 10 mg/LHistorical result, sampled August 15, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Wisconsin to EPA.
- FluorideLatest: 0.783 mg/L · 140 of 236 samples detected · highest 1.03 mg/L (July 9, 2014) · legal limit 4 mg/LHistorical result, sampled December 2, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Wisconsin to EPA.
- Total trihalomethanesLatest: 7.99 µg/L · 68 of 68 samples detected · highest 13.37 µg/L (July 16, 2019) · legal limit 80 µg/LHistorical result, sampled October 15, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Wisconsin to EPA.
Sources
Data refreshed November 14, 2026- Safe Drinking Water Information System (SDWIS/Fed), ECHO downloadsUS EPA, Safe Drinking Water Information System (SDWIS/Fed), via ECHO
- Service Line Inventory report (SDWIS Federal Reporting Services)U.S. EPA, SDWIS/Fed Service Line Inventory report
- Six-Year Review 4 compliance monitoring data (2012-2019)U.S. EPA, Six-Year Review 4 compliance monitoring data (2012-2019), as reported by state drinking water programs
- Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) occurrence dataUS EPA, UCMR 5 occurrence data
- Drinking Water System data: contaminant resultsWisconsin Department of Natural Resources, Drinking Water System data
No government agency endorses TapDepth. See something wrong? Contact us