This is what Ebeling WSC reported to the state and EPA. It is not a test of the water at your tap, which your home's pipes and fixtures can change. Information only, not medical advice. Data sources and method
Depth Score · partial
Below limits, some above health goals
TapDepth's rating of public data, not a safety finding. As of Nov 2026, method 1.2. How the score works
From results reported by Ebeling WSC, sampled Dec 2023 to Apr 2026. Not a test of your tap.
- Health55%91
- Pipes20%Not included
Not in our data yet: utilities' lead service line inventories haven't been added.
- Track record15%37
- Everyday water10%Not included
No recent hardness or dissolved solids results.
How this score was worked out
Health
Each substance's average over its latest year of samples, compared with its legal limit and health goal. Up to 10 points off each. Volatile organic chemicals count as one group, by the worst one, and so do pesticides and industrial chemicals, and nitrate with nitrate + nitrite. Lead and copper use the 90th percentile of home tap samples and the action level.
| Substance | Average | Legal limit | Health goal | Rule | Points |
|---|---|---|---|---|---|
| Arsenic | 3.2 µg/L (1 sample, Aug 2025 to Aug 2025) | 10 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | −4.6 |
| Nitrate (as nitrogen) | 3.28 mg/L (2 samples, Aug 2025 to Apr 2026) | 10 mg/L | 10 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Fluoride | 2.43 mg/L (1 sample, Aug 2025 to Aug 2025) | 4 mg/L | 4 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Benzene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Carbon tetrachloride | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichlorobenzene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 600 µg/L | 600 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,4-Dichlorobenzene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 75 µg/L | 75 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichloroethane | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1-Dichloroethylene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 7 µg/L | 7 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| cis-1,2-Dichloroethylene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 70 µg/L | 70 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| trans-1,2-Dichloroethylene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Dichloromethane | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichloropropane | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Ethylbenzene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 700 µg/L | 700 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Chlorobenzene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Styrene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Tetrachloroethylene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Toluene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 1,000 µg/L | 1,000 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2,4-Trichlorobenzene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 70 µg/L | 70 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1,1-Trichloroethane | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 200 µg/L | 200 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1,2-Trichloroethane | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 3 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Trichloroethylene | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Vinyl chloride | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 2 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Xylenes (total) | 0 µg/L (1 sample, Apr 2026 to Apr 2026) | 10,000 µg/L | 10,000 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Antimony | 0 µg/L (1 sample, Aug 2025 to Aug 2025) | 6 µg/L | 6 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Barium | 0.11 mg/L (1 sample, Aug 2025 to Aug 2025) | 2 mg/L | 2 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Beryllium | 0 µg/L (1 sample, Aug 2025 to Aug 2025) | 4 µg/L | 4 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Cadmium | 0 µg/L (1 sample, Aug 2025 to Aug 2025) | 5 µg/L | 5 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Chromium (total) | 0 µg/L (1 sample, Aug 2025 to Aug 2025) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Cyanide | 0 µg/L (1 sample, Jul 2024 to Jul 2024) | 200 µg/L | 200 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Mercury (inorganic) | 0 µg/L (1 sample, Aug 2025 to Aug 2025) | 2 µg/L | 2 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Selenium | 5 µg/L (1 sample, Aug 2025 to Aug 2025) | 50 µg/L | 50 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Thallium | 0 µg/L (1 sample, Aug 2025 to Aug 2025) | 2 µg/L | 0.5 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Lead | 5.36 µg/L (1 sample, Dec 2023 to Dec 2023) | 15 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | −4.9 |
Track record
100, minus 25 for each health-based violation in the last 5 years (here 1), 10 for each from 5 to 10 years ago (2) and 3 for each missed or late test, report or notice (6). Boil water notices aren't in our data yet.
Everyday water
No recent hardness or dissolved solids results.
PFAS
PFAS are not counted until EPA's PFAS limits take effect. EPA currently lists April 2029 for PFOA and PFOS, and has proposed moving that to 2031. PFAS results are shown separately.
PFAS outlook: upcoming EPA limits
Not yet enforceable. EPA lists April 2029 and has proposed 2031.
We don't have PFOA or PFOS results for this system. EPA's national PFAS sampling covered mostly larger systems, and other results may not be public yet. This doesn't mean PFAS were or weren't found. Under EPA's rule, community water systems must finish initial PFAS testing by 2027.
The PFAS outlook is not a compliance finding and does not change the Depth Score. It covers PFOA and PFOS, the two PFAS limits EPA has said it plans to keep. Results from untreated source water are left out.
substances with a recent sample
in the latest samples
since Nov 2016
paperwork and monitoring, since Nov 2016
Current results
34 substancesSubstances with drinking water limits, from the last six years of samples. Highest recent sample shown.
- Arsenic3.2 µg/LReported by Ebeling WSC, sampled August 6, 2025.EPA's health goal for this substance is zero.Sample point: point EP001 TRT-TAPWhat is arsenic?
- Nitrate (as nitrogen)3.2 mg/L
- Fluoride2.43 mg/L
- BenzeneNot detected (below 0.5 µg/L)
- Carbon tetrachlorideNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is carbon tetrachloride?
- 1,2-DichlorobenzeneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,2-Dichlorobenzene?
- 1,4-DichlorobenzeneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,4-Dichlorobenzene?
- 1,2-DichloroethaneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,2-Dichloroethane?
- 1,1-DichloroethyleneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,1-Dichloroethylene?
- cis-1,2-DichloroethyleneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is cis-1,2-Dichloroethylene?
- trans-1,2-DichloroethyleneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is trans-1,2-Dichloroethylene?
- DichloromethaneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is dichloromethane?
- 1,2-DichloropropaneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,2-Dichloropropane?
- EthylbenzeneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is ethylbenzene?
- ChlorobenzeneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is chlorobenzene?
- StyreneNot detected (below 0.5 µg/L)
- TetrachloroethyleneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is tetrachloroethylene?
- TolueneNot detected (below 0.5 µg/L)
- 1,2,4-TrichlorobenzeneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,2,4-Trichlorobenzene?
- 1,1,1-TrichloroethaneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,1,1-Trichloroethane?
- 1,1,2-TrichloroethaneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is 1,1,2-Trichloroethane?
- TrichloroethyleneNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is trichloroethylene?
- Vinyl chlorideNot detected (below 0.5 µg/L)Reported by Ebeling WSC, sampled April 22, 2026.Sample point: point EP001 TRT-TAPWhat is vinyl chloride?
- Xylenes (total)Not detected (below 0.5 µg/L)
- AntimonyNot detected (below 1 µg/L)
- Barium0.11 mg/L
- BerylliumNot detected (below 1 µg/L)
- CadmiumNot detected (below 1 µg/L)
- Chromium (total)Not detected (below 1 µg/L)Reported by Ebeling WSC, sampled August 6, 2025.Total chromium includes chromium-3 and chromium-6. EPA's 100 µg/L limit covers the total, and there's no separate federal limit for chromium-6.Sample point: point EP001 TRT-TAPWhat is chromium (total)?
- CyanideNot detected (below 20 µg/L)
- Mercury (inorganic)Not detected (below 0.2 µg/L)
- Selenium5 µg/L
- ThalliumNot detected (below 1 µg/L)
- Lead5.36 µg/LReported by Ebeling WSC, sampled December 31, 2023.EPA's health goal for this substance is zero.Sample point: 90th percentile of home tap samples the system collected, Jan 2021 to Dec 2023What is lead?
Other monitored substances
1 substanceSubstances EPA asked systems to test for to decide future rules. Most have no limit yet.
- Sodium57.8 mg/L
Taste, smell and look
7 substancesGuidelines for taste and appearance. These are not health limits.
- Aluminum0.036 mg/L
- Chloride48.7 mg/L
- Iron0.0723 mg/L
- Manganese0.0036 mg/L
- SilverNot detected (below 0.001 mg/L)
- Sulfate26.9 mg/L
- ZincNot detected (below 0.005 mg/L)
These figures were reported by the water system to its regulators. They are not a test of the water at this address. Compliance is judged on averages over time, so one sample above a limit does not by itself mean a system is out of compliance. For a test of your own tap, use a state-certified laboratory. Units: µg/L is micrograms per liter, the same as parts per billion (ppb); mg/L is milligrams per liter, the same as parts per million (ppm).
Violations since Nov 2016
Recorded by the state and EPAHealth-based
A drinking water limit or treatment requirement was not met.
- Violation recorded by the state for Oct 2024LEAD AND COPPER RULE REVISIONS · Lead and Copper Rule Revisions · Status: unaddressed
- Violation recorded by the state for Jul 2021 to Sep 2021Nitrate · Nitrate Rule · Status: resolved
- Violation recorded by the state for Apr 2021 to Jun 2021Nitrate · Nitrate Rule · Status: resolved
Testing and reporting
A required test or report was missed or late. This is about paperwork and monitoring, and does not by itself mean the water was unsafe.
- Missed or late test or report (Jul 2025 to Jan 2026). Doesn't by itself mean the water was unsafeConsumer Confidence Rule · Consumer Confidence Rule · Status: resolved
- Missed or late test or report (Oct 2024). Doesn't by itself mean the water was unsafeLEAD AND COPPER RULE REVISIONS · Lead and Copper Rule Revisions · Status: unaddressed
- Missed or late test or report (Dec 2023 to Apr 2026). Doesn't by itself mean the water was unsafeLead and Copper Rule · Lead and Copper Rule · Status: resolved
- Missed or late test or report (Oct 2019 to Oct 2020). Doesn't by itself mean the water was unsafeLead and Copper Rule · Lead and Copper Rule · Status: resolved
Notices and other requirements
A required notice to customers was missed or late.
- Public Notification Violation for NPDWR Violation (May 2025 to Jan 2026)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Mar 2021 to Aug 2021)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
On the map
Nearby water providers, colored by Depth ScoreLoading the map…
Open on the mapYearly water quality report
We don't have a link to this provider's yearly water quality report yet. Providers that serve homes send one to customers every year by July 1, and you can ask the provider for a copy.
Where the water comes from
No water purchases from another system are recorded.
Service lines (pipes from the water main to buildings)
No service line inventory on file with EPA.
A lead or galvanized service line can add lead to water, but it doesn't mean there is lead in your water. These counts cover the whole system, not your address. Ask your water system whether your home's line is on its inventory.
Historical results (2012-2019)
Lab results states sent EPA for 2012-2019, compiled by EPA for its Six-Year Review of drinking water rules, not for compliance decisions. They are more than six years old, so they may not reflect the water today, and they are never mixed with current results.
- ArsenicLatest: 3.3 µg/L · 3 of 3 samples detected · highest 3.64 µg/L (January 30, 2013) · legal limit 10 µg/LHistorical result, sampled July 30, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
- Nitrate (as nitrogen)Latest: 4.15 mg/L · 29 of 29 samples detected · highest 8.23 mg/L (July 30, 2019) · legal limit 10 mg/LHistorical result, sampled October 3, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
- FluorideLatest: 2.3 mg/L · 3 of 3 samples detected · highest 2.67 mg/L (January 20, 2016) · legal limit 4 mg/LHistorical result, sampled July 30, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
- Total trihalomethanesLatest: 4.88 µg/L · 2 of 2 samples detected · highest 4.88 µg/L (July 30, 2019) · legal limit 80 µg/LHistorical result, sampled July 30, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
Sources
Data refreshed November 14, 2026- Safe Drinking Water Information System (SDWIS/Fed), ECHO downloadsUS EPA, Safe Drinking Water Information System (SDWIS/Fed), via ECHO
- Six-Year Review 4 compliance monitoring data (2012-2019)U.S. EPA, Six-Year Review 4 compliance monitoring data (2012-2019), as reported by state drinking water programs
- Drinking Water Viewer: sample results (exported by hand)Texas Commission on Environmental Quality, Drinking Water Viewer data
No government agency endorses TapDepth. See something wrong? Contact us