This is what City of Anna reported to the state and EPA. It is not a test of the water at your tap, which your home's pipes and fixtures can change. Information only, not medical advice. Data sources and method
Depth Score · partial
Below limits, some above health goals
TapDepth's rating of public data, not a safety finding. As of Nov 2026, method 1.2. How the score works
From results reported by City of Anna, North Texas Mwd Leonard Wtp, Greater Texoma Utility Authority, sampled May 2024 to Sep 2026. Not a test of your tap.
- Health55%98
- Pipes20%Not included
Not in our data yet: utilities' lead service line inventories haven't been added.
- Track record15%20
- Everyday water10%Not included
No recent hardness or dissolved solids results.
How this score was worked out
Health
Each substance's average over its latest year of samples, compared with its legal limit and health goal. Up to 10 points off each. Volatile organic chemicals count as one group, by the worst one, and so do pesticides and industrial chemicals, and nitrate with nitrate + nitrite. Lead and copper use the 90th percentile of home tap samples and the action level.
| Substance | Average | Legal limit | Health goal | Rule | Points |
|---|---|---|---|---|---|
| Arsenic | 0 µg/L (5 samples, May 2024 to Feb 2025) | 10 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Nitrate (as nitrogen) | 0.079 mg/L (4 samples, Jul 2025 to Jul 2026) | 10 mg/L | 10 mg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Fluoride | 0.9198 mg/L (5 samples, May 2024 to Feb 2025) | 4 mg/L | 4 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Benzene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Carbon tetrachloride | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichlorobenzene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 600 µg/L | 600 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,4-Dichlorobenzene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 75 µg/L | 75 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichloroethane | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1-Dichloroethylene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 7 µg/L | 7 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| cis-1,2-Dichloroethylene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 70 µg/L | 70 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| trans-1,2-Dichloroethylene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Dichloromethane | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2-Dichloropropane | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Ethylbenzene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 700 µg/L | 700 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Chlorobenzene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Styrene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Tetrachloroethylene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Toluene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 1,000 µg/L | 1,000 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,2,4-Trichlorobenzene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 70 µg/L | 70 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1,1-Trichloroethane | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 200 µg/L | 200 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| 1,1,2-Trichloroethane | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 3 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Trichloroethylene | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 5 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Vinyl chloride | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 2 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Xylenes (total) | 0 µg/L (2 samples, Jul 2025 to Jul 2025) | 10,000 µg/L | 10,000 µg/L (EPA health goal (MCLG)) | At or below the health goal | Not counted (group) |
| Antimony | 0 µg/L (5 samples, May 2024 to Feb 2025) | 6 µg/L | 6 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Barium | 0.0304 mg/L (5 samples, May 2024 to Feb 2025) | 2 mg/L | 2 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Beryllium | 0 µg/L (5 samples, May 2024 to Feb 2025) | 4 µg/L | 4 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Cadmium | 0 µg/L (5 samples, May 2024 to Feb 2025) | 5 µg/L | 5 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Chromium (total) | 0.6 µg/L (5 samples, May 2024 to Feb 2025) | 100 µg/L | 100 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Cyanide | 0 µg/L (1 sample, Jul 2026 to Jul 2026) | 200 µg/L | 200 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Mercury (inorganic) | 0 µg/L (5 samples, May 2024 to Feb 2025) | 2 µg/L | 2 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Nitrite (as nitrogen) | 0.376 mg/L (1 sample, Feb 2025 to Feb 2025) | 1 mg/L | 1 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Selenium | 0 µg/L (5 samples, May 2024 to Feb 2025) | 50 µg/L | 50 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Thallium | 0 µg/L (7 samples, May 2024 to Feb 2025) | 2 µg/L | 0.5 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Lead | 0 µg/L (1 sample, Sep 2026 to Sep 2026) | 15 µg/L | 0 µg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Bromate | 0.25 µg/L (10 samples, May 2025 to Apr 2026) | 10 µg/L | 0 µg/L (EPA health goal (MCLG)) | Health goal is zero | −2.2 |
| Chlorite | 0.0013 mg/L (36 samples, May 2025 to May 2026) | 1 mg/L | 0.8 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
| Nitrate + nitrite (as nitrogen) | 0.354 mg/L (1 sample, Dec 2024 to Dec 2024) | 10 mg/L | 10 mg/L (EPA health goal (MCLG)) | At or below the health goal | 0 |
Track record
100, minus 25 for each health-based violation in the last 5 years (here 1), 10 for each from 5 to 10 years ago (1) and 3 for each missed or late test, report or notice (15). Boil water notices aren't in our data yet.
Everyday water
No recent hardness or dissolved solids results.
PFAS
PFAS are not counted until EPA's PFAS limits take effect. EPA currently lists April 2029 for PFOA and PFOS, and has proposed moving that to 2031. PFAS results are shown separately.
PFAS outlook: upcoming EPA limits
Not yet enforceable. EPA lists April 2029 and has proposed 2031.
PFOA and PFOS were not detected (below the lab's reporting limit) in the latest year of samples in our data.
Latest sample November 18, 2025. Highest sample point one-year average, counted the rule's way: 0 ng/L (12 samples at 4 sample points, Feb 2025 to Nov 2025).
Latest sample November 18, 2025. Highest sample point one-year average, counted the rule's way: 0 ng/L (12 samples at 4 sample points, Feb 2025 to Nov 2025).
Bars show the latest sample. The line marks EPA's upcoming limit of 4 ng/L each.
Reported by City of Anna, sampled November 18, 2025.
Averaged the way EPA's rule describes (each sample point's one-year average), using the results we have. The rule counts results below 4 ng/L (parts per trillion) as zero in that average. Our data may not include every sample point, and only regulators decide compliance.
The PFAS outlook is not a compliance finding and does not change the Depth Score. It covers PFOA and PFOS, the two PFAS limits EPA has said it plans to keep. Results from untreated source water are left out.
substances with a recent sample
in the latest samples
since Nov 2016
paperwork and monitoring, since Nov 2016
Current results
38 substancesSubstances with drinking water limits, from the last six years of samples. Highest recent sample shown.
- ArsenicNot detected (below 1 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is arsenic?
- Nitrate (as nitrogen)0.364 mg/LReported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is nitrate?
- Fluoride1.61 mg/L
- BenzeneNot detected (below 0.5 µg/L)
- Carbon tetrachlorideNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is carbon tetrachloride?
- 1,2-DichlorobenzeneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,2-Dichlorobenzene?
- 1,4-DichlorobenzeneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,4-Dichlorobenzene?
- 1,2-DichloroethaneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,2-Dichloroethane?
- 1,1-DichloroethyleneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,1-Dichloroethylene?
- cis-1,2-DichloroethyleneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is cis-1,2-Dichloroethylene?
- trans-1,2-DichloroethyleneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is trans-1,2-Dichloroethylene?
- DichloromethaneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is dichloromethane?
- 1,2-DichloropropaneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,2-Dichloropropane?
- EthylbenzeneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is ethylbenzene?
- ChlorobenzeneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is chlorobenzene?
- StyreneNot detected (below 0.5 µg/L)
- TetrachloroethyleneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is tetrachloroethylene?
- TolueneNot detected (below 0.5 µg/L)
- 1,2,4-TrichlorobenzeneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,2,4-Trichlorobenzene?
- 1,1,1-TrichloroethaneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,1,1-Trichloroethane?
- 1,1,2-TrichloroethaneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is 1,1,2-Trichloroethane?
- TrichloroethyleneNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is trichloroethylene?
- Vinyl chlorideNot detected (below 0.5 µg/L)Reported by City of Anna, sampled July 30, 2025.Sample point: point EP002 TRT-TAPWhat is vinyl chloride?
- Xylenes (total)Not detected (below 0.5 µg/L)
- AntimonyNot detected (below 1 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is antimony?
- Barium0.05 mg/L
- BerylliumNot detected (below 1 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is beryllium?
- CadmiumNot detected (below 1 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is cadmium?
- Chromium (total)1.6 µg/LReported by City of Anna, sampled May 29, 2024.Total chromium includes chromium-3 and chromium-6. EPA's 100 µg/L limit covers the total, and there's no separate federal limit for chromium-6.Sample point: point EP004 TRT-TAPWhat is chromium (total)?
- Cyanide137 µg/LReported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is cyanide?
- Mercury (inorganic)Not detected (below 0.2 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is mercury?
- Nitrite (as nitrogen)0.376 mg/LReported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is nitrite?
- SeleniumNot detected (below 5 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is selenium?
- ThalliumNot detected (below 1 µg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is thallium?
- LeadNot detectedReported by City of Anna, sampled September 28, 2026.Sample point: 90th percentile of home tap samples the system collected, Jan 2026 to Dec 2026What is lead?
- BromateNot detected (below 5 µg/L)Reported by North Texas Mwd Leonard Wtp, sampled April 14, 2026.Tested by North Texas Mwd Leonard Wtp, which supplies this system.Sample point: point EP001 TRT-TAPWhat is bromate?
- ChloriteNot detected (below 0.005 mg/L)Reported by North Texas Mwd Leonard Wtp, sampled May 4, 2026.Tested by North Texas Mwd Leonard Wtp, which supplies this system.Sample point: point DS01 CLO2NEP001What is chlorite?
- Nitrate + nitrite (as nitrogen)0.354 mg/LReported by Greater Texoma Utility Authority, sampled December 3, 2024.Tested by Greater Texoma Utility Authority, which supplies this system.Sample point: point EP001 TRT-TAPWhat is nitrate + nitrite?
PFAS ("forever chemicals")
29 substancesEPA set limits for some PFAS in 2024. They aren't enforceable yet, so they're shown as upcoming limits and never in warning colors.
- PFOANot detected (below 4 ng/L)
- PFOSNot detected (below 4 ng/L)
- PFHxSNot detected (below 3 ng/L)
- PFNANot detected (below 4 ng/L)
- HFPO-DA (GenX)Not detected (below 5 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is genX (HFPO-DA)?
- PFBSNot detected (below 3 ng/L)
- PFBA5.3 ng/LReported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFPeANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFHxANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFHpANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFDANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFUnANot detected (below 2 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFDoANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFTrDANot detected (below 7 ng/L)Reported by City of Anna, sampled December 4, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFTANot detected (below 8 ng/L)Reported by City of Anna, sampled December 4, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFPeSNot detected (below 4 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFHpSNot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFMPANot detected (below 4 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFMBANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- PFEESANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- NFDHANot detected (below 20 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- ADONANot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- 9Cl-PF3ONSNot detected (below 2 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- 11Cl-PF3OUdSNot detected (below 5 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- 4:2 FTSNot detected (below 3 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- 6:2 FTSNot detected (below 5 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- 8:2 FTSNot detected (below 5 ng/L)Reported by City of Anna, sampled November 18, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- NEtFOSAANot detected (below 5 ng/L)Reported by City of Anna, sampled December 4, 2025.Sample point: Powell Pump StationWhat is other PFAS?
- NMeFOSAANot detected (below 6 ng/L)Reported by City of Anna, sampled December 4, 2025.Sample point: Powell Pump StationWhat is other PFAS?
Other monitored substances
2 substancesSubstances EPA asked systems to test for to decide future rules. Most have no limit yet.
- Lithium24.5 µg/LReported by City of Anna, sampled August 14, 2025.Sample point: South Grayson Pump StationWhat is lithium?
- Sodium247 mg/L
Taste, smell and look
7 substancesGuidelines for taste and appearance. These are not health limits.
- Aluminum0.031 mg/L
- Chloride24.3 mg/L
- Iron0.0506 mg/L
- Manganese0.005 mg/L
- SilverNot detected (below 0.001 mg/L)Reported by City of Anna, sampled February 10, 2025.Sample point: point EP005 TRT-TAPWhat is silver?
- Sulfate100 mg/L
- ZincNot detected (below 0.005 mg/L)
These figures were reported by the water system to its regulators. They are not a test of the water at this address. Compliance is judged on averages over time, so one sample above a limit does not by itself mean a system is out of compliance. For a test of your own tap, use a state-certified laboratory. Units: ng/L is nanograms per liter, the same as parts per trillion (ppt); µg/L is micrograms per liter, the same as parts per billion (ppb); mg/L is milligrams per liter, the same as parts per million (ppm).
Violations since Nov 2016
Recorded by the state and EPAHealth-based
A drinking water limit or treatment requirement was not met.
- Violation recorded by the state for Oct 2024 to Jun 2025LEAD AND COPPER RULE REVISIONS · Lead and Copper Rule Revisions · Status: resolved
- Violation recorded by the state for Jul 2019 to Sep 2019TTHM · Stage 2 Disinfectants and Disinfection Byproducts Rule · Status: resolved
Testing and reporting
A required test or report was missed or late. This is about paperwork and monitoring, and does not by itself mean the water was unsafe.
- Missed or late test or report (Sep 2025 to Feb 2026). Doesn't by itself mean the water was unsafeLead and Copper Rule · Lead and Copper Rule · Status: resolved
- Missed or late test or report (Jul 2025 to Jan 2026). Doesn't by itself mean the water was unsafeConsumer Confidence Rule · Consumer Confidence Rule · Status: resolved
- Missed or late test or report (Jan 2025 to Jun 2025). Doesn't by itself mean the water was unsafeLead and Copper Rule · Lead and Copper Rule · Status: resolved
- Missed or late test or report (Oct 2024 to Jun 2025). Doesn't by itself mean the water was unsafeLEAD AND COPPER RULE REVISIONS · Lead and Copper Rule Revisions · Status: resolved
- Missed or late test or report (Dec 2021 to Apr 2022). Doesn't by itself mean the water was unsafeE. COLI · Ground Water Rule · Status: resolved
- Missed or late test or report (Dec 2021 to Apr 2022). Doesn't by itself mean the water was unsafeE. COLI · Ground Water Rule · Status: resolved
Show 2 more
- Missed or late test or report (Oct 2021 to Apr 2022). Doesn't by itself mean the water was unsafeE. COLI · Ground Water Rule · Status: resolved
- Missed or late test or report (Oct 2017 to Oct 2018). Doesn't by itself mean the water was unsafeLead and Copper Rule · Lead and Copper Rule · Status: resolved
Notices and other requirements
A required notice to customers was missed or late.
- Public Notification Violation for NPDWR Violation (Apr 2026 to Apr 2026)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (May 2025 to Jun 2025)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Mar 2023 to May 2023)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Mar 2023 to May 2023)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Mar 2023 to May 2023)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Oct 2018 to Dec 2018)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
Show 1 more
- Public Notification Violation for NPDWR Violation (Aug 2018 to Jul 2019)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
On the map
Nearby water providers, colored by Depth ScoreLoading the map…
Open on the mapYearly water quality report
We don't have a link to this provider's yearly water quality report yet. Providers that serve homes send one to customers every year by July 1, and you can ask the provider for a copy.
Where the water comes from
City of Anna buys water from:
- Greater Texoma Utility AuthorityTX0910148
When this system has no result of its own for a substance, we show its supplier's and say so.
Service lines (pipes from the water main to buildings)
As reported by CITY OF ANNA to Texas, in EPA's records as of the third quarter of 2026: 0 lead, 0 galvanized needing replacement, 0 material not yet identified, 11,588 non-lead.
Galvanized needing replacement: galvanized lines that are or were connected to lead pipe, which the rule says must be replaced.
Non-lead counts may be incomplete: EPA doesn't require them until November 2027.
A lead or galvanized service line can add lead to water, but it doesn't mean there is lead in your water. These counts cover the whole system, not your address. Ask your water system whether your home's line is on its inventory.
U.S. EPA, SDWIS/Fed Service Line Inventory report, data as of November 21, 2026
Historical results (2012-2019)
Lab results states sent EPA for 2012-2019, compiled by EPA for its Six-Year Review of drinking water rules, not for compliance decisions. They are more than six years old, so they may not reflect the water today, and they are never mixed with current results.
- ArsenicLatest: not detected · 0 of 8 samples detected · legal limit 10 µg/LHistorical result, sampled March 21, 2018. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
- Nitrate (as nitrogen)Latest: 0.0342 mg/L · 31 of 32 samples detected · highest 1.02 mg/L (June 29, 2015) · legal limit 10 mg/LHistorical result, sampled August 15, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
- FluorideLatest: 2.33 mg/L · 13 of 13 samples detected · highest 2.33 mg/L (March 21, 2018) · legal limit 4 mg/LHistorical result, sampled March 21, 2018. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
- Total trihalomethanesLatest: 37.8 µg/L · 27 of 29 samples detected · highest 109 µg/L (June 21, 2019) · legal limit 80 µg/LWas above the legal limit in this sample (June 21, 2019).Historical result, sampled November 7, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Texas to EPA.
Sources
Data refreshed November 14, 2026- Safe Drinking Water Information System (SDWIS/Fed), ECHO downloadsUS EPA, Safe Drinking Water Information System (SDWIS/Fed), via ECHO
- Service Line Inventory report (SDWIS Federal Reporting Services)U.S. EPA, SDWIS/Fed Service Line Inventory report
- Six-Year Review 4 compliance monitoring data (2012-2019)U.S. EPA, Six-Year Review 4 compliance monitoring data (2012-2019), as reported by state drinking water programs
- Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) occurrence dataUS EPA, UCMR 5 occurrence data
- Drinking Water Viewer: sample results (exported by hand)Texas Commission on Environmental Quality, Drinking Water Viewer data
No government agency endorses TapDepth. See something wrong? Contact us