This is what Montoursville Water Company reported to the state and EPA. It is not a test of the water at your tap, which your home's pipes and fixtures can change. Information only, not medical advice. Data sources and method
Depth Score
Not enough data for a score
TapDepth's rating of public data, not a safety finding. As of Nov 2026, method 1.2. How the score works
Fewer than 3 substances with a legal limit have recent results, so there is not enough data for a score.
Capped at 49: Copper's 90th percentile of home tap samples was above the action level (1300 µg/L) in its latest monitoring period (ending Sep 2025).
PFAS outlook: upcoming EPA limits
Not yet enforceable. EPA lists April 2029 and has proposed 2031.
At least one sample point's one-year average in our data is above EPA's upcoming 4 ng/L limit. That limit isn't enforceable yet.
Latest sample October 15, 2024. Highest sample point one-year average, counted the rule's way: 3.3 ng/L (4 samples at 2 sample points, Oct 2023 to Oct 2024).
Latest sample October 15, 2024. Highest sample point one-year average, counted the rule's way: 6.05 ng/L (4 samples at 2 sample points, Oct 2023 to Oct 2024).
Bars show the latest sample. The line marks EPA's upcoming limit of 4 ng/L each.
Reported by Montoursville Water Company, sampled October 15, 2024.
Averaged the way EPA's rule describes (each sample point's one-year average), using the results we have. The rule counts results below 4 ng/L (parts per trillion) as zero in that average. Our data may not include every sample point, and only regulators decide compliance.
The PFAS outlook is not a compliance finding and does not change the Depth Score. It covers PFOA and PFOS, the two PFAS limits EPA has said it plans to keep. Results from untreated source water are left out.
substances with a recent sample
in the latest samples
since Nov 2016
paperwork and monitoring, since Nov 2016
Current results
2 substancesSubstances with drinking water limits, from the last six years of samples. Highest recent sample shown.
- Lead1.08 µg/LReported by Montoursville Water Company, sampled September 30, 2025.EPA's health goal for this substance is zero.Sample point: 90th percentile of home tap samples the system collected, Jun 2025 to Sep 2025What is lead?
- Copper1,722 µg/LReported by Montoursville Water Company, sampled September 30, 2025.Sample point: 90th percentile of home tap samples the system collected, Jun 2025 to Sep 2025What is copper?
PFAS ("forever chemicals")
29 substancesEPA set limits for some PFAS in 2024. They aren't enforceable yet, so they're shown as upcoming limits and never in warning colors.
- PFOA6.6 ng/LReported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is PFOA?
- PFOS12.1 ng/LReported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is PFOS?
- PFHxS3.1 ng/LReported by Montoursville Water Company, sampled April 15, 2024.Sample point: Wells 4 and 5 and Sylvan DellWhat is PFHxS?
- PFNANot detected (below 4 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is PFNA?
- HFPO-DA (GenX)Not detected (below 5 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is genX (HFPO-DA)?
- PFBSNot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is PFBS?
- PFBANot detected (below 5 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFPeA4.2 ng/LReported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFHxA3.3 ng/LReported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFHpANot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFDANot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFUnANot detected (below 2 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFDoANot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFTrDANot detected (below 7 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFTANot detected (below 8 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFPeSNot detected (below 4 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFHpSNot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFMPANot detected (below 4 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFMBANot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- PFEESANot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- NFDHANot detected (below 20 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- ADONANot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- 9Cl-PF3ONSNot detected (below 2 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- 11Cl-PF3OUdSNot detected (below 5 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- 4:2 FTSNot detected (below 3 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- 6:2 FTSNot detected (below 5 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- 8:2 FTSNot detected (below 5 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- NEtFOSAANot detected (below 5 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
- NMeFOSAANot detected (below 6 ng/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is other PFAS?
Other monitored substances
1 substanceSubstances EPA asked systems to test for to decide future rules. Most have no limit yet.
- LithiumNot detected (below 9 µg/L)Reported by Montoursville Water Company, sampled October 15, 2024.Sample point: Well #2What is lithium?
These figures were reported by the water system to its regulators. They are not a test of the water at this address. Compliance is judged on averages over time, so one sample above a limit does not by itself mean a system is out of compliance. For a test of your own tap, use a state-certified laboratory. Units: ng/L is nanograms per liter, the same as parts per trillion (ppt); µg/L is micrograms per liter, the same as parts per billion (ppb).
Violations since Nov 2016
Recorded by the state and EPAHealth-based
A drinking water limit or treatment requirement was not met.
None recordedTesting and reporting
A required test or report was missed or late. This is about paperwork and monitoring, and does not by itself mean the water was unsafe.
- Missed or late test or report (Jul 2025 to Sep 2025). Doesn't by itself mean the water was unsafeTotal Haloacetic Acids (HAA5) · Stage 2 Disinfectants and Disinfection Byproducts Rule · Status: resolved
- Missed or late test or report (Jul 2025 to Sep 2025). Doesn't by itself mean the water was unsafeTTHM · Stage 2 Disinfectants and Disinfection Byproducts Rule · Status: resolved
- Missed or late test or report (Jan 2024 to Jan 2024). Doesn't by itself mean the water was unsafeGroundwater Rule · Ground Water Rule · Status: resolved
- Missed or late test or report (Oct 2023 to Dec 2023). Doesn't by itself mean the water was unsafeTotal Polychlorinated Biphenyls (PCB) · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (May 2023 to May 2023). Doesn't by itself mean the water was unsafeChlorine · Stage 1 Disinfectants and Disinfection Byproducts Rule · Status: resolved
- Missed or late test or report (Jan 2023 to Mar 2023). Doesn't by itself mean the water was unsafe2,3,7,8-TCDD · Synthetic Organic Chemicals · Status: archived
Show 39 more
- Missed or late test or report (Jan 2023 to Mar 2023). Doesn't by itself mean the water was unsafeTotal Polychlorinated Biphenyls (PCB) · Synthetic Organic Chemicals · Status: archived
- Missed or late test or report (Jun 2022 to Jun 2022). Doesn't by itself mean the water was unsafeGroundwater Rule · Ground Water Rule · Status: resolved
- Missed or late test or report (Jul 2020 to Sep 2020). Doesn't by itself mean the water was unsafeTotal Haloacetic Acids (HAA5) · Stage 2 Disinfectants and Disinfection Byproducts Rule · Status: resolved
- Missed or late test or report (Jul 2020 to Sep 2020). Doesn't by itself mean the water was unsafeTTHM · Stage 2 Disinfectants and Disinfection Byproducts Rule · Status: resolved
- Missed or late test or report (Jul 2020 to Sep 2020). Doesn't by itself mean the water was unsafe2,3,7,8-TCDD · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jul 2020 to Sep 2020). Doesn't by itself mean the water was unsafeTotal Polychlorinated Biphenyls (PCB) · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Mar 2020). Doesn't by itself mean the water was unsafe2,3,7,8-TCDD · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Mar 2020). Doesn't by itself mean the water was unsafeTotal Polychlorinated Biphenyls (PCB) · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeEndrin · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeBHC-GAMMA · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeMethoxychlor · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeToxaphene · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeDalapon · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeDiquat · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeEndothall · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeGlyphosate · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeDi(2-ethylhexyl) adipate · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeOXAMYL · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeSimazine · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeDi(2-ethylhexyl) phthalate · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafePicloram · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeDinoseb · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeHexachlorocyclopentadiene · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeCarbofuran · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeAtrazine · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeLASSO · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeHeptachlor · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeHeptachlor epoxide · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafe2,4-D · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafe2,4,5-TP · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeHEXACHLOROBENZENE · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeBenzo(a)pyrene · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafePentachlorophenol · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafe1,2-DIBROMO-3-CHLOROPROPANE · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeETHYLENE DIBROMIDE · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (Jan 2020 to Dec 2020). Doesn't by itself mean the water was unsafeChlordane · Synthetic Organic Chemicals · Status: resolved
- Missed or late test or report (May 2019 to May 2019). Doesn't by itself mean the water was unsafeGroundwater Rule · Ground Water Rule · Status: resolved
- Missed or late test or report (Jul 2018 to Sep 2018). Doesn't by itself mean the water was unsafeConsumer Confidence Rule · Consumer Confidence Rule · Status: resolved
- Missed or late test or report (Oct 2017 to Dec 2017). Doesn't by itself mean the water was unsafeCombined Uranium · Radionuclides and Revised Rad Rule · Status: resolved
Notices and other requirements
A required notice to customers was missed or late.
- Public Notification Violation for NPDWR Violation (Feb 2025 to Apr 2025)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Apr 2024 to Jun 2024)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Apr 2024 to Jun 2024)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
- Public Notification Violation for NPDWR Violation (Jul 2023 to Jun 2024)Public Notice · Public Notice Rule and Revised PN Rule · Status: resolved
On the map
Nearby water providers, colored by Depth ScoreLoading the map…
Open on the mapYearly water quality report
We don't have a link to this provider's yearly water quality report yet. Providers that serve homes send one to customers every year by July 1, and you can ask the provider for a copy.
Where the water comes from
No water purchases from another system are recorded.
Service lines (pipes from the water main to buildings)
As reported by MONTOURSVILLE WATER COMPANY to Pennsylvania, in EPA's records as of the third quarter of 2026: 0 lead, 18 galvanized needing replacement, 631 material not yet identified, 1,553 non-lead.
Galvanized needing replacement: galvanized lines that are or were connected to lead pipe, which the rule says must be replaced.
Non-lead counts may be incomplete: EPA doesn't require them until November 2027.
A lead or galvanized service line can add lead to water, but it doesn't mean there is lead in your water. These counts cover the whole system, not your address. Ask your water system whether your home's line is on its inventory.
U.S. EPA, SDWIS/Fed Service Line Inventory report, data as of November 21, 2026
Historical results (2012-2019)
Lab results states sent EPA for 2012-2019, compiled by EPA for its Six-Year Review of drinking water rules, not for compliance decisions. They are more than six years old, so they may not reflect the water today, and they are never mixed with current results.
- ArsenicLatest: not detected · 0 of 3 samples detected · legal limit 10 µg/LHistorical result, sampled August 3, 2018. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Pennsylvania to EPA.
- Nitrate (as nitrogen)Latest: 2.2 mg/L · 9 of 9 samples detected · highest 2.2 mg/L (August 7, 2019) · legal limit 10 mg/LHistorical result, sampled August 7, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Pennsylvania to EPA.
- FluorideLatest: not detected · 1 of 3 samples detected · highest 0.16 mg/L (July 24, 2012) · legal limit 4 mg/LHistorical result, sampled August 3, 2018. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Pennsylvania to EPA.
- Total trihalomethanesLatest: 2.3 µg/L · 5 of 11 samples detected · highest 16.6 µg/L (August 4, 2017) · legal limit 80 µg/LHistorical result, sampled August 7, 2019. More than six years old, so it may not reflect the water today. From EPA's Six-Year Review 4 data, as reported by Pennsylvania to EPA.
Sources
Data refreshed November 14, 2026- Safe Drinking Water Information System (SDWIS/Fed), ECHO downloadsUS EPA, Safe Drinking Water Information System (SDWIS/Fed), via ECHO
- Service Line Inventory report (SDWIS Federal Reporting Services)U.S. EPA, SDWIS/Fed Service Line Inventory report
- Six-Year Review 4 compliance monitoring data (2012-2019)U.S. EPA, Six-Year Review 4 compliance monitoring data (2012-2019), as reported by state drinking water programs
- Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) occurrence dataUS EPA, UCMR 5 occurrence data
No government agency endorses TapDepth. See something wrong? Contact us